It carries a 23 kW rating at 230 V 60 °C and an 11 kW AC-2 rating at 400 V, making it suitable for moderate-duty motor switching on pumps, fans, and conveyors. The 690 V rated insulation voltage and pollution degree 3 suit it for standard industrial environments where dust and conductive deposits are present.
Termination and wiring — screw terminals for main and auxiliary circuits
Solid wire acceptance: 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), max 2x (0.75…4 mm²). Stranded wire: 2x (0.75…25 mm²), and solid or stranded: 2x (0.75…16 mm²). The 16 mm² minimum at 40 °C and 60 °C indicates the minimum conductor size for full rated current — don't undersize the feed. Dimensions: 112 mm height, 73 mm width, 115 mm depth. The 73 mm width is the panel space it occupies on the DIN rail — plan for that when laying out a row of contactors and overloads. IP20 on the front, IP00 at the terminals — the terminal area is not finger-safe, so panel guarding or a cover is needed in accessible enclosures.
Coil and switching data
Coil operates at 50 Hz and 60 Hz, with voltage tolerance of 0.8…1.1 at 50 Hz and 0.85…1.1 at 60 Hz. Maximum mechanical switching frequency at AC-1 is 1,000 operations per hour. Auxiliary contact ratings at various voltages: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, 3 A at 400 V (–). These are the make/break capacities for the built-in auxiliary contacts — useful for PLC inputs or pilot lights.