It carries a 23 kW resistive rating at 230 V (AC-1) and an 11 kW motor rating at 400 V (AC-2) — the AC-2 figure is the one that governs for standard squirrel-cage motors on conveyor or pump duty, so size your motor branch circuit against that number, not the higher AC-1 value.
The control circuit takes 0.5–1.5 mm² solid or 0.75–2.5 mm² stranded. Strip length and ferrule sizing follow standard practice — no oddball pitch here.
The IP20 front enclosure keeps fingers off live parts inside the panel; the terminals themselves are IP00, meaning the panel enclosure provides the final touch protection.