Dimensions are 146 mm high, 93 mm wide, and 139 mm deep — the 93 mm width is the key panel fill factor when laying out a row of S3 contactors.
Solid wire acceptance: 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), max. 2x (0.75... 4 mm²). Stranded main conductors: 2x (10... 50 mm²). For the main contacts, AWG cables 2x (10... 1/0) are accepted. At 40 °C and 60 °C, the minimum permissible conductor cross-section is 35 mm². The short-circuit protection coordination (type 2) requires a fuse gL/gG: 125 A.