Solid wire acceptance: 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), max. 2x (0.75... 4 mm²). Stranded: 2x (10... 50 mm²). At 60 °C minimum permissible conductor is 35 mm².
Coil and switching characteristics
Coil operates at 50 Hz (rated 48 V) and 60 Hz (rated 48 V). The operating range at 50 Hz is 0.8 to 1.1 times rated voltage; at 60 Hz it is 0.85 to 1.1. Maximum mechanical switching rate at AC-1 duty is 1 000 operations per hour. Typical mechanical life is 10 000 000 operations.
Auxiliary contacts are rated for DC switching: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V. These are the figures to use when sizing the control circuit — the DC ratings drop sharply with voltage, so a 24 VDC pilot light is fine, but a 220 VDC interlock will need a contactor with higher DC ratings or a separate relay.
The part carries a substance prohibitance date of 05/01/2012, aligning with RoHS and REACH compliance. Standard documentation includes the datasheet, CE declaration, and UL/CSA file information — request these at time of RFQ if your quality team needs them for the BOM package.