Panel fit and mounting constraints
The 3RT1364-6AE36 is a size S10 SIRIUS contactor with a 140 mm width, 196 mm height, and 153 mm depth — the footprint determines the DIN-rail or backplate real estate it occupies in the panel. Fastening is by screw fixing, not snap-on DIN rail. The mounting position allows vertical surface installation with ±180° rotation and up to ±30° forward/backward tilt at 0° rotation, or standing orientation. These are the minimum air gaps to adjacent components or enclosure walls for proper heat dissipation and arc containment.
Coil and auxiliary contact specs
The magnet coil is screw-type terminals and operates on AC voltage. Switching times are 45...80 ms for both AC and DC operation. The auxiliary switch block provides 2 instantaneous contacts. Up to 2 auxiliary switch blocks can be attached.
Wire termination and environmental range
Terminal capacity accepts solid or stranded wire: 1x (1...4 mm²) or 2x (1...4 mm²) per clamp. This covers common control wiring sizes from 18 AWG to 12 AWG. The contactor is rated for use in unconditioned enclosures within those limits.