The key motor ratings are 22 kW at AC-2 duty at 400 V, 29.9 kW at 500 V, and 38.2 kW at 690 V. Auxiliary contact ratings are provided across common control voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC. The DC switching capability at 220 V is notably low — 0.3 A — so if you are switching a DC coil or solenoid at that voltage, verify the inrush does not exceed this.
Dimensions are 146 mm high, 70 mm wide, and 139 mm deep. The front has IP20 protection with the cover or box terminal fitted; the terminal body itself is IP00. Wire ranges for the main circuit: solid accepts 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded accepts 2x (10 to 50 mm²). At 40 °C the minimum permissible conductor is 50 mm²; at 60 °C it drops to 35 mm² — derate the wire if the panel runs hot.
RoHS compliance date is noted as May 1, 2012, covering the substance prohibitance deadline.