Specifications

3RT1466-6AP36-ZX95 — Identification
ParameterValue
Contactor frame sizeS10
3RT1466-6AP36-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1466-6AP36-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.9
Rated value @ 50 Hz220 ... 240 V
3RT1466-6AP36-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1466-6AP36-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 500 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegR: 500 A (690 V, 100 kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT1466-6AP36-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionConnection bar
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew fixing
Side-by-side mountingYes
3RT1466-6AP36-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1466-6AP36-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1466-6AP36-ZX95 — Mechanical
ParameterValue
Width145 mm
Height210 mm
Depth202 mm
3RT1466-6AP36-ZX95 — Specifications
ParameterValue
At AC40 ... 80 ms

Product details

SIRIUS S10 Contactor, 220–240 V AC/DC Coil

The Siemens 3RT1466-6AP36-ZX95 is a SIRIUS S10-size contactor with a 220–240 V AC/DC coil terminated at screw-type terminals. The coil pickup and dropout both fall within 40–80 ms across AC and DC supplies, so the switching timing is consistent regardless of supply type—useful when the control circuit is shared between AC relays and a DC PLC output card. An auxiliary switch is included on the unit, rated at 10 A at 24 V, 6 A at 230 V, and derating to 0.3 A at 220 V DC, which governs what downstream loads the auxiliary can directly switch without an interposing relay.

Mechanical Endurance and Mounting Flexibility

Wiring and Panel Fit

Power circuit wiring accepts stranded conductors from 70 to 240 mm²—sized for the S10 frame's current-carrying capacity. Control-circuit terminals accept solid or stranded wire in two parallel entries per clamp: 2× (0.5–1.5 mm²) or 2× (0.75–2.5 mm²), with a maximum of 2× (0.75–4 mm²). The enclosure measures 210 mm high × 145 mm wide × 202 mm deep. Mounting is via screw fixing through an 11 mm hole—no DIN-rail adapter on this variant.

Frequently asked questions

Where can I buy 3RT1466-6AP36-ZX95 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is 3RT1466-6AP36-ZX95's listed depth?

The depth is 202 mm.

What wire sizes does the control circuit accept?

The control-circuit terminals accept solid or stranded wire: 2× (0.5–1.5 mm²), 2× (0.75–2.5 mm²), or max 2× (0.75–4 mm²).

What is the closest functional alternative to 3RT1466-6AP36-ZX95?

The 3RT1264-6AP36-0KA1 is a peer in the same SIRIUS family. The key difference is the coil voltage—the 3RT1466 carries a 220–240 V AC/DC coil, while the 3RT1264 variant uses a different coil rating. Panel footprint and auxiliary configuration should be verified against the existing cutout and wiring before substitution.