SIRIUS S10 contactor — 3RT1466-6NB36
The coil accepts 21-27.3 V AC/DC, with screw-type terminals for the magnet coil. An auxiliary switch is integrated. Rated for a typical mechanical life of 10,000,000 operations, this contactor handles auxiliary contact loads up to 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 6 A at 230 V (-). The arcing time is 10-15 ms. Full-scale value is 1.1, with an initial value of 0.8.
Dimensions are 210 mm height, 145 mm width, 202 mm depth. Fastening is by screw fixing through a single 11 mm diameter hole. Up to 4 auxiliary contact blocks can be attached.
Wiring and conductor ranges
Solid conductors: 2x (0.5-1.5 mm²), 2x (0.75-2.5 mm²), max 2x (0.75-4 mm²). Stranded conductors: 70-240 mm².