Integrator's first look
Its coil accepts 96... 127 V AC/DC, so one part covers both control supply types without a separate rectifier or coil changeout. The screw-type magnet coil terminals match standard panel wiring practices; main power terminals accept stranded cable from 70 up to 240 mm², sized for the output of a 200+ A motor circuit. Mounting is via screw fixing through a single 11 mm hole, with the contactor body measuring 210 mm high by 145 mm wide by 202 mm deep.
Panel integration checklist
Screw fixing through an 11 mm hole — plan for a single-point mount on a backplate or sub-panel, not DIN rail. The 145 mm width and 202 mm depth mean it occupies roughly the footprint of a 200 A frame breaker; leave the 20 mm forward clearance for arc gases. Main cable: 70... 240 mm² stranded — use a hydraulic crimper for lug termination; the terminal size matches standard two-hole or single-hole lug patterns for this current class. The auxiliary switch is already attached, so no separate aux block purchase is needed for basic N/O or N/C feedback.