SIRIUS S10 contactor — 3RT1467-6SF36-3PA0
Coil rated 96-127 V AC/DC with screw-type terminals, and the listed MTBF of 75 a gives a reliability baseline for maintenance planning — this is the mean time between failures for the contactor itself, not the load it switches. Mounting is via screw fixing on a vertical surface; the contactor can be rotated ±90° or tilted ±22.5° forward/back, so panel layout has flexibility.
Coil and auxiliary contacts
The magnet coil uses screw-type terminals, accepting 2x (0.5-1.5 mm²) or 2x (0.75-2.5 mm²) solid/stranded, max 2x 4 mm². Coil pickup time is 115-130 ms on both AC and DC, with arcing time 10-15 ms. An auxiliary switch is included, rated 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 220 V — these are the contact ratings for the aux, not the main poles.
Dimensions and clearances
Physical envelope: 210 mm height, 145 mm width, 202 mm depth. The single 11 mm mounting hole is for the screw fixing. Main power terminals accept stranded cable 70-240 mm².