SIRIUS power contactor, size S00 — 24 VDC coil, screw terminals
The 24 VDC coil draws its holding current from a standard 24 VDC supply; dropout occurs below the 0.85 initial-value threshold, so verify your control voltage stays above that during brownout conditions. Main circuit connections use screw-type terminals, accepting solid or stranded copper: 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or max 2x (0.75...4 mm²). The auxiliary contacts — one NO and one NC — are each rated 9 A, and share the same terminal style.
DC switching capability across the voltage range
This contactor carries a DC-1 rated switching curve: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, and 0.8 A at 440 V. The arcing time runs 10...15 ms; the operate time at DC is 7...10 ms. For DC loads, the inductive time constant of the circuit governs contact erosion — the listed currents assume resistive or slightly inductive DC loads, not heavily suppressed arcs.