Skip to main content
Siemens 3RT1516-2AP60 — Contactors

Siemens SIRIUS 3RT1516-2AP60 Power Contactor, Size S00, 10 A

MPN3RT1516-2AP60

Siemens SIRIUS power contactor, size S00, 3RT1516-2AP60, 10 A at 24 V rated value, screw and snap-on DIN rail mount, spring-loaded terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1516-2AP60 — Identification
ParameterValue
Contactor frame sizeS00
3RT1516-2AP60 — Ratings & Performance
ParameterValue
Rated value @ 400 V3 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1516-2AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz5.1 V·A
Rated value @ 50 Hz220 V
3RT1516-2AP60 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts2
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1516-2AP60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1516-2AP60 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Side-by-side mountingYes
3RT1516-2AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1516-2AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
3RT1516-2AP60 — Mechanical
ParameterValue
Width45 mm
Height60 mm
Depth72 mm
3RT1516-2AP60 — Specifications
ParameterValue
At AC4 ... 30 ms

Product details

Mounting and termination

The main current circuit uses spring-loaded terminals, accepting 2x (0.25 to 2.5 mm²) solid or stranded conductors. The contactor is 45 mm wide, 60 mm high, and 72 mm deep.

Sourcing posture

The spring-loaded terminals and S00 footprint make it a direct fit for panels originally specified with the 3RT1016-2AP02, provided the coil voltage and auxiliary contact configuration match — the physical envelope and mounting rail are identical.

Frequently asked questions

Will the 3RT1516-2AP60 drop into a panel specified for the 3RT1016-2AP02?

Yes, both are size S00 contactors with the same 45 mm width and snap-on DIN rail mounting per DIN EN 50022. The physical fit is identical, but verify the coil voltage and auxiliary contact configuration match your BOM.

What are the key dimensions of the 3RT1516-2AP60?

The contactor is 45 mm wide, 60 mm high, and 72 mm deep.

What type of terminals does the main circuit use?

The main current circuit uses spring-loaded terminals that accept 2x (0.25 to 2.5 mm²) solid or stranded conductors.

MPN
3RT1516-2AP60