It switches resistive and lightly inductive loads up to 12 A per pole (AC-1), with a coil designed for 100 V at 50 Hz or 100-110 V at 60 Hz.
The 12 A per pole (NO/NC) is the continuous thermal current (Ith) — the contactor can carry that current in free air without exceeding temperature rise limits. For motor loads, derate to the AC-3 rating (not listed here, but typically around 5-7 A for S00). The 6 kV rated impulse withstand voltage on main and auxiliary circuits means it coordinates with standard 400 V distribution panels without additional surge suppression. Arcing time runs 10-15 ms; the AC switching time (4-30 ms) covers coil pickup and dropout — fast enough for most PLC-controlled sequences.
Panel integration
Altitude rated to 2 000 m without derating.