The 24 VDC coil draws 4.4 VA at 50 Hz and holds at 24 V rated value, switching up to 10 A at 24 V (AC-1 duty). The contactor mounts via screw or snap-on onto 35 mm DIN rail per EN 50022, with a width of 45 mm, height 57.5 mm, and depth 72 mm — fits standard panel cutouts without crowding adjacent devices.
DIN rail integration and wiring
The mounting position allows vertical surface with +/-180° rotation and +/-30° tilt front/back, so panel layout is flexible. Screw-type terminals on the main circuit accept solid wire 2x (0.5...1.5 mm²) and 2x (0.75...2.5 mm²), max 2x (0.75...4 mm²).