The coil draws 5.1 VA at 50 Hz and holds in at 24 VDC nominal; it switches inductive loads with an arcing time of 10 to 15 ms and a make/break duration of 4 to 30 ms at AC.
The main contacts are rated for switching at several voltage levels: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.8 A at 440 V — those are the currents it can interrupt under AC-1 resistive load. The auxiliary contacts, both NO and NC, each carry 12 A continuously. Impulse withstand voltage is 6 kV for both the main and auxiliary circuits, so it coordinates with standard motor branch circuit protection without adding a separate surge gap. Wire terminations are screw-type on the main circuit, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) per terminal. That covers standard panel-building wire sizes without needing ferrule adapters. It can be mounted with the vertical surface rotated 180° or tilted ±30° front-to-back, which helps when the panel layout is tight.