Power contactor for panel builders — SIRIUS size S00
Main circuit contacts are spring-loaded terminals accepting 2x (0.25–2.5 mm²) solid or stranded wire, rated for AC-12 duty at 10 A maximum — suitable for switching resistive or lightly inductive loads in distribution and machine control. Coil draws 10 A at 24 V rated value (4.4 VA at 50 Hz), with pickup times of 4–30 ms AC and arcing time 10–15 ms — fast enough for relay-logic or PLC-driven outputs without external suppression in most panels.
Snap-on DIN rail — panel integration note
Mounting position allows vertical surface with ±180° rotation and ±30° tilt forward/back — useful when the contactor sits on a swing-out panel or angled subplate. Side-by-side mounting is supported without derating, with a 6 mm clearance to adjacent devices recommended for heat dissipation. Front protection is IP20 — safe for enclosed panels; the contactor body is not sealed against washdown. Operating temperature range -25 to +60 °C, storage -55 to +80 °C, with altitude limit 2 000 m without derating.