It carries a 35 A rated operational current per NO and NC main contact at 24 V DC, per the datasheet.
The S0 footprint measures 61 mm wide by 85 mm tall by 101 mm deep, which is the standard slot for this frame class.
The 35 A rating at 24 V DC on the main contacts means this contactor can switch DC loads up to that current — important for battery-backed or DC-bus applications. For AC auxiliary circuits, the contact ratings step down with voltage: 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. The minimum DC switching capability is 16 mA at 24 V, which covers low-power PLC inputs and pilot lights.
Protection and environmental limits
Short-circuit protection requires a gL/gG fuse rated at 35 A for type 2 coordination. Arcing time is specified at 10 to 15 ms, and DC operating time between 13 and 40 ms.