It switches resistive and motor loads in control panels, with a mechanical life of 10 million operations typical. The coil pulls 15 VA at 50 Hz; arcing time runs 10 to 15 ms, so it clears fast enough for most motor-starting duty.
The vertical mounting surface allows +/-180° rotation and +/-30° tilt front-to-back, so you can orient it for wire routing without derating. Side-by-side mounting is permitted — no extra gap needed between units. At 73 mm wide, 112 mm tall, and 115 mm deep, it fits a standard S2 footprint.
AWG equivalents for the main contacts go from 18 to 2 AWG. The magnet coil also terminates at screw terminals — no push-in or spring-cage here, so keep a screwdriver handy for panel wiring.
This is an active SIRIUS catalog line. For volume or blanket orders, submit an RFQ with target quantity and delivery window.