Skip to main content
Siemens 3RT1647-1AN61 — Contactors

Siemens 3RT1647-1AN61 Capacitor Contactor, AC-6 50 kVAr, 200

MPN3RT1647-1AN61

Siemens SIRIUS 3RT1 series capacitor contactor, 3RT1647-1AN61, AC-6 rated 50 kVAr at 400 V, 200 V AC 50/60 Hz coil, 3-pole NO main contacts, 1 NO auxiliary, screw terminals, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1647-1AN61 — Control & Coil
ParameterValue
Rated value @ 50 Hz200 ... 200 V
3RT1647-1AN61 — Contacts & Poles
ParameterValue
Main NO contacts3
3RT1647-1AN61 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1647-1AN61 — Mechanical
ParameterValue
Width70 mm
Height167 mm
Depth183 mm

Product details

The Siemens 3RT1647-1AN61 is a SIRIUS capacitor contactor built for switching capacitive loads — specifically rated AC-6 at 50 kVAr / 400 V. That AC-6 duty class means it's designed to handle the inrush current from power-factor correction capacitor banks without welding the contacts. The coil pulls 200 V AC at both 50 and 60 Hz, so it lands on a standard control transformer secondary in European panels.

Lifecycle and replacement

This order code is a phased-out product. The manufacturer's designated successor is the SIRIUS 3RT2 series, with preferred replacement type 3RT2636-1NP35. The official successor is a drop-in functional replacement for new designs, but verify the coil voltage and auxiliary contact configuration against your panel schematic before committing.

The 70 mm width and 183 mm depth fit a standard S3-size contactor footprint — panel cutouts and gland-plate layouts for the SIRIUS 3RT1 family carry over.

Protection is IP00 on the terminals and IP20 on the front with the cover or box terminal installed — so it's panel-internal only, not for washdown or outdoor use without an enclosure. RoHS compliance date is noted as 05/01/2012, indicating the part was RoHS-compliant from that date forward.

Frequently asked questions

What is the AC-6 rating on this contactor?

The AC-6 rating is 50 kVAr at 400 V. AC-6 is the IEC utilization category for switching capacitor banks — the contactor is designed to handle the high inrush current and restrike voltage that come with capacitive loads, which a standard AC-3 motor contactor may not survive long-term.

What coil voltage does 3RT1647-1AN61 need?

It requires 200 V AC at 50 Hz or 200...220 V AC at 60 Hz. The coil frequency range is 50...60 Hz. This is a standard European control voltage; verify your panel's control transformer taps before wiring.

Will 3RT1647-1AN61 drop into a panel specified around 3RT1044-1FB46?

The 3RT1647-1AN61 shares the same 70 mm width and screw-and-snap-on DIN-rail mounting method, so the mechanical footprint is compatible. However, the coil voltage differs (200 V AC vs 24 V DC on the 3RT1044-1FB46), and the 3RT1647 is a capacitor contactor while the 3RT1044 is a general-purpose power contactor. The auxiliary contact count also differs (1 NO vs 2 NO/2 NC). Rewiring of the control circuit and possibly the main power circuit would be required.

Where can I buy 3RT1647-1AN61?

This phased-out part is sourced through independent distribution channels. Submit an RFQ for current availability and pricing — the quote confirms the supply position at that time.

MPN
3RT1647-1AN61