What the 3RT1926-2FL11 does in the panel
The timer is adjustable from 0.05 to 1 s, with a recovery time of 150 ms between cycles, so it is suited for sequencing delays in conveyor start-up or pump staging where the load must not see simultaneous energisation. It is a purely electromechanical ON-delay block — no OFF-delay, no pulse-shaping, no star-delta logic — so the buyer gets a single-function delay that is simple to specify and swap.
Coil voltage and contact ratings
The auxiliary contacts are rated 3 A maximum, with specific interrupting capacities: 1 A at 24 V, 0.2 A at 125 V, and 0.1 A at 250 V — these are the wetting current limits for the silver-alloy contacts, not the thermal rating; the 24 V figure is the one to check if the switch drives a PLC input or a small relay.