It carries a 24 VDC screw-type coil, three main poles rated for 20 to 12 A, and an integrated auxiliary switch. The part snaps onto a 35 mm DIN rail per DIN EN 60715, with ±180° rotation allowed on a vertical surface and ±22.5° tilt forward or backward. Rated switching frequencies vary by duty: 1 000 ops/h at AC-1 (resistive), 750 ops/h at AC-2 and AC-3 (motor starting/running), and 250 ops/h at AC-4 (plugging/inching). The AC-3e rating also sits at 750 ops/h. Typical mechanical life is 30 000 000 operations.
DIN-rail footprint and wiring
The S00 envelope measures 45 mm wide, 58 mm high, and 73 mm deep. The screw-type terminals accept solid or stranded conductors from 0.5 to 4 mm², with dual-wire capacity for 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². These dimensions and wiring specs determine panel layout and terminal strip matching.
The built-in auxiliary switch is rated for switching at various control voltages: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.14 A at 440 V. These ratings cover typical PLC and relay interface levels.
Environmental range
The wide storage range is a handling limit, not a running condition.