SIRIUS S00 power contactor — 3RT2015-1AM22
It snaps onto a 35 mm DIN rail per DIN EN 60715 and fits a compact 45 mm wide footprint — 58 mm tall, 73 mm deep — so it slides into tight panel layouts without crowding adjacent devices. The coil draws 0.25 A at both 50 Hz and 60 Hz, and the contactor's rated operational current at 24 V is 10 A. That 10 A figure governs resistive loads at the coil voltage; for motor duty the AC-3 switching frequency tops out at 750 operations per hour, while AC-4 (inching / plugging) is limited to 250 cycles per hour — a constraint that matters for reversing or jogging applications.
Mounting and wiring flexibility
Clearance requirements are modest: 10 mm upward and forward, 10 mm downward, 6 mm at the sides. Screw terminals accept solid or stranded wire from 0.5 to 4 mm², and also take two conductors per clamp: 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), or 2x 4 mm². That daisy-chain capability saves terminal blocks when feeding through the same phase.