Skip to main content
Siemens 3RT2015-1AN22 — Contactors

Siemens 3RT2015-1AN22 SIRIUS Power Contactor, S00, 24V Coil

MPN3RT2015-1AN22
Active

Siemens SIRIUS 3RT2015-1AN22 power contactor, size S00, 24 VDC coil, screw-type terminals, snap-on 35 mm DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2015-1AN22 — Identification
ParameterValue
Contactor frame sizeS00
3RT2015-1AN22 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V6.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V0.75 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2015-1AN22 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz220 V
3RT2015-1AN22 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2015-1AN22 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2015-1AN22 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2015-1AN22 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2015-1AN22 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2015-1AN22 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm
3RT2015-1AN22 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

It snaps onto a 35 mm DIN rail per DIN EN 60715, and its mounting position is flexible — it can be rotated ±180° on a vertical surface and tilted ±22.5° forward or backward.

The 3RT2015-1AN22 is rated for 10 A at 24 V, 2 A at 48 V, and 3 A at 400 V for its auxiliary contacts — these are the switching limits for control circuits at those voltages. For the main contacts, the mechanical service life is typical 30 million operations, and the maximum operating frequency varies by duty: 1,000 cycles/hour for AC-1 (resistive loads), 750 cycles/hour for AC-3 (squirrel-cage motor starting), and 250 cycles/hour for AC-4 (plugging/inching). The contactor measures 45 mm wide, 58 mm high, and 73 mm deep, with clearance requirements of 10 mm upward, 10 mm forward, 10 mm downward, and 6 mm at the side.

Frequently asked questions

What are the key dimensions for panel layout?

The contactor is 45 mm wide, 58 mm high, and 73 mm deep. It requires 10 mm clearance above, below, and in front, and 6 mm clearance on the sides for proper ventilation and arc containment.

What wire sizes does the screw terminal accept?

The main contact terminals accept solid or stranded wire from 0.5 to 4 mm². They also accept two conductors per terminal: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm².

Does this contactor include an auxiliary contact block?

Yes, the 3RT2015-1AN22 comes with an integrated auxiliary switch as standard equipment.

MPN
3RT2015-1AN22