Siemens 3RT2015-2AB01 SIRIUS Power Contactor — Integrator's Spec Recap
The contactor snaps onto a 35 mm DIN rail per DIN EN 60715, and the mounting position allows +/-180° rotation on a vertical surface, plus +/-22.5° tilt forward and backward — useful when you're fitting it into a tight panel and need to orient the coil terminals for wire routing.
The AC-1 (resistive) rating is 1000 operations per hour maximum; AC-3 (motor starting) and AC-3e are both 750 ops/h, and AC-4 (plugging/reversing) drops to 250 ops/h. That 6 mm side clearance is tighter than some competing S00 frames, so check your DIN-rail spacing if you're packing contactors side-by-side.
Deployment Context — Panel Integration
The operating temperature range is -25 to +60 °C, storage from -55 to +80 °C — fine for most indoor industrial environments, but if your panel sits near a furnace or in a refrigerated area, the -25 °C lower limit is the constraint.