The coil is 24 VDC, and the contactor carries a 10 A rated operational current at 24 V and 3 A at 400 V. Mechanical life is rated at 30,000,000 operating cycles typical, and the contactor can handle up to 1000 switching operations per hour in AC-1 duty, 750/h in AC-3, and 250/h in AC-4. That makes it a right-sized spec for moderate-duty conveyor or pump starts where you don't need a larger frame.
Dimensions are 45 mm wide, 70 mm high, and 73 mm deep. That helps when you're squeezing it into a tight corner of the enclosure.
Rated operational currents vary by voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.14 A at 440 V (–). At 230 V it's rated 0.75 hp. Arcing time is 4 to 15 ms at AC, with a narrower 10 to 15 ms window for the main contacts. The 50/60 Hz coil draw is 0.25 A at both frequencies.