At 45 mm wide and 70 mm high, it fits the standard S00 footprint. Depth is 121 mm — watch the gland plate clearance if you're packing relays behind it.
The AC-3 maximum is 750 operations per hour, and AC-4 drops to 250 per hour — that's the heavy inching/jogging limit. Arcing time runs 10 to 15 ms. The 24 VDC coil draws 6 A at rated value; at 48 V it's 2 A. These numbers tell you the contactor is sized for moderate-duty motor switching, not continuous resistive loads at full nameplate.