The coil is rated 24 V DC, and the contactor carries a DC-13 switching capacity of 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. For AC motor duty (AC-3), the contactor is rated for 750 switching operations per hour; for resistive loads (AC-1), it handles up to 1 000 cycles per hour. The arcing time falls between 10 and 15 ms, and the DC switching delay is 7 to 13 ms. Mechanical life is typically 30 000 000 operations. Conductor cross-section accepts 0.5 to 4 mm² solid or stranded, and 2x (0.5 to 4 mm²) for double ferrule.

Siemens 3RT2015-2BB42-ZW97 SIRIUS Contactor, S00, 24 VDC
Siemens SIRIUS power contactor, size S00, 24 V DC coil, spring-type terminals, 3RT2015-2BB42-ZW97.
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S00 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 6.5 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 0.75 hp |
| Rated value @ 24 V | 10 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | DC |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA) |
| Short-circuit coordination type 2, fuse | gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | spring-loaded terminals |
| Aux. / control circuit connection | spring-loaded terminals |
| Conductor cross-section, solid | 0.5 ... 4 mm² |
| Conductor cross-section, solid or stranded | 2x (0,5 ... 4 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 2.5 mm²) |
| Mounting method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 30 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 70 mm |
| Depth | 73 mm |
Product details
Frequently asked questions
What are the key ratings for this contactor?
The coil is 24 V DC. DC-13 switching capacity is 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. AC-3 switching frequency is 750 cycles/h, AC-1 is 1 000 cycles/h. Mechanical life is typically 30 000 000 operations.
What are the mounting dimensions and clearances?
The contactor measures 70 mm high, 45 mm wide, and 73 mm deep. Clearances required: 10 mm upward, 10 mm forward, 10 mm downward, and 6 mm at the side.
What conductor sizes does the spring terminal accept?
Solid or stranded conductors from 0.5 to 4 mm², and 2x (0.5 to 4 mm²) for double ferrule.
Does this contactor include an auxiliary switch?
Yes, it includes an auxiliary switch. The main contacts are rated 20 to 12 A.