It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, with a 45 mm width that fits standard panel fill patterns. The 24 VDC coil is rated for 10 A at 24 V, with the auxiliary switch integrated.
DIN rail fit and clearances
At 45 mm wide and 73 mm deep, the contactor occupies a single 45 mm DIN slot — no overhang on a standard 35 mm rail. Required clearances: 10 mm upwards, 10 mm forwards, 10 mm downwards, 6 mm at the side. The mounting position allows +/-180° rotation on a vertical surface and +/-22.5° tilt forward/backward, which helps when fitting into a crowded gland plate or backpanel.
Switching capacity and operating limits
Rated for 10 A at 24 VDC and 3 A at 400 VAC. The DC switching curve drops to 2 A at 48 V, 0.9 A at 125 V, and 0.3 A at 220 V — useful when specifying for DC control circuits or auxiliary loads. Maximum mechanical switching frequency: 1 000 cycles/hour at AC-1, 750 at AC-2/AC-3, 250 at AC-4. Arcing time runs 10 to 15 ms, with a 4 to 15 ms operating time at AC. Operating temperature range -25 to +60 °C; storage range -55 to +80 °C.