The 45 mm width and 58 mm height fit standard S00 contactor spacing in a control panel.
Coil and Auxiliary Contact Specifications
Power consumption at both 50 and 60 Hz is 0.24 A. Its auxiliary contact ratings vary by voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.14 A at 440 V, 4.8 A at 480 V, and 2 A at 500 V. For motor loads, it carries a 0.75 hp rating at 230 V. Arcing time is 4 to 15 ms at AC, with a typical arcing duration of 10 to 15 ms.
Switching Frequency and Lifecycle
Maximum switching frequency depends on duty class: 1,000 operations per hour at AC-1, 750 per hour at AC-2, AC-3, and AC-3e, and 250 per hour at AC-4. The typical mechanical service life is 30,000,000 operations.
As an active-production part, the 3RT2015-4AK62 is quoted to order through Siemens distribution. The part is a direct fit for any panel designed around the S00 contactor footprint and 35 mm DIN rail.