Coil pulls 24 VDC at 10 A rated; on the 480 VAC side it carries 4.8 A. That 24 VDC pickup is the one you spec for a PLC-driven output — holds down to about 18 V before dropout, typical for this class.
That 45 mm width is a standard module slot — one TE (17.5 mm) would be tight; this is a 2.5-TE-wide device. Arcing time runs 10–15 ms at AC; switching frequencies range from 250 ops/h at AC-4 up to 1000 ops/h at AC-1. The magnet coil termination uses a ring cable lug connection — keep a ring terminal crimper in the van; a fork or pin terminal won't seat right.