The contactor is rated for AC-3 switching (motor starting) at up to 750 operating cycles per hour, and AC-4 (plugging/reversing) at 250 cycles per hour. The auxiliary contact block switches 10 A at 24 V and derates to 0.2 A at 440 V — important to check your control voltage when sizing the auxiliary circuit.
The contactor accepts solid or stranded wire from 0.5 to 4 mm² on the main terminals, with double-wire capacity up to 2x 4 mm². Minimum clearances: 10 mm upward/downward, 10 mm forward, 6 mm at the side.