The 10 A rated operational current at 24 V (AC-1 duty) means it handles resistive loads up to that current; for motor duty (AC-3), the rated current is lower, so size for the actual motor FLA, not the contactor's maximum.
The 45 mm width and 58 mm height fit standard S00 footprint enclosures. Depth of 73 mm leaves clearance for wiring and auxiliary contact blocks. Accepts solid or stranded conductors from 0.5 to 4 mm², with dual-wire capability up to 2x 2.5 mm².
Switching performance and thermal limits
Maximum switching frequency varies by duty: 1 000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor start/run), and 250/h at AC-4 (plugging/inching).