Wire range accepts 0.5 to 4 mm² solid or stranded, including 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), and 2x 4 mm² — covers most control-circuit terminations without needing a ferrule.
Ratings & Duty
The auxiliary switch is built in. Switching frequency: AC-1 (resistive) up to 1,000 operations/hour, AC-2 and AC-3 (motor starting/running) up to 750 ops/hour, AC-4 (plugging/inching) up to 250 ops/hour. Rated operational current at 24 V is 10 A; at 400 V it's 3 A. Mechanical life typical is 30 million operations.