Skip to main content
Siemens 3RT2016-1BB42-1AA0 — Contactors

Siemens 3RT2016-1BB42-1AA0 SIRIUS Power Contactor, Size S00,

MPN3RT2016-1BB42-1AA0
Active

Siemens SIRIUS 3RT2016-1BB42-1AA0, Size S00 power contactor, 24 VDC coil, screw-type terminals, 3-pole, auxiliary switch included.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2016-1BB42-1AA0 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1BB42-1AA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1BB42-1AA0 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-1BB42-1AA0 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1BB42-1AA0 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1BB42-1AA0 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1BB42-1AA0 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-1BB42-1AA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1BB42-1AA0 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm

Product details

Part Identity & Mounting

The Siemens SIRIUS 3RT2016-1BB42-1AA0 is a Size S00 power contactor with a 24 VDC coil, designed for screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715.

For higher DC voltages, the rating drops to 2 A at 48 V and 60 V, and 1 A at 110 V — a typical derating curve for DC switching where arc extinction is harder. Switching frequency is duty-dependent: 1,000 cycles/hour for AC-1 resistive loads, 750 cycles/hour for AC-2 and AC-3 motor loads, and 250 cycles/hour for AC-4 plugging/inching duty. The AC-3e rating also sits at 750 cycles/hour. This tells the panel builder that high-inertia or frequent jogging applications need the AC-4 derating. Mechanical service life is 30,000,000 cycles typical, with main contact electrical life specified at 20 to 12 cycles depending on load. The 30-million figure means the actuator mechanism outlasts most panel designs; the electrical life is what governs replacement intervals in heavy cycling.

Environmental & Integration

The 60 °C ceiling is common for panel interiors near drives or transformers — verify ambient inside the enclosure stays below that. Wire cross-section accepts solid or stranded conductors from 0.5 to 4 mm², with dual-wire capacity for 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm². The screw terminals are standard for panel wiring — no special tooling needed beyond a screwdriver.

Frequently asked questions

What are the key dimensions for panel layout?

The contactor measures 73 mm depth, 45 mm width, and 58 mm height. It mounts on 35 mm DIN rail with 10 mm clearance needed upwards, forwards, and downwards, and 6 mm at the side.

What wire sizes does the screw terminal accept?

Solid or stranded conductors from 0.5 to 4 mm². For dual-wire termination, it accepts 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm².

What is the auxiliary contact rating at 24 VDC?

The auxiliary contact is rated 10 A at 24 V. For higher DC voltages, derate to 2 A at 48 V or 60 V, 1 A at 110 V, and 0.9 A at 125 V.

MPN