Specifications

3RT2016-1BB42-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1BB42-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1BB42-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-1BB42-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1BB42-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1BB42-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1BB42-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-1BB42-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1BB42-ZX95 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm

Product details

An auxiliary switch is built in — no separate add-on to track. The contactor mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, and the mounting position allows +/-180° rotation on a vertical surface plus +/-22.5° tilt forward/backward. That means it fits a panel layout without fighting the orientation.

Panel fit and clearances

At 45 mm wide, 58 mm tall, and 73 mm deep, this contactor sits in a standard S00 footprint. That keeps the arc chamber vented and the terminals accessible for a screwdriver. Wire range accepts 0.5 to 4 mm² solid or stranded, and up to 2x 4 mm² or 2x (0.5 to 1.5 mm²) for paralleled feeds — no holes in the box for a terminal adapter.

Rated switching frequency varies by duty: 1 000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor start/run), and 250/h at AC-4 (plugging/inching). The AC-3e rating also sits at 750/h. The auxiliary contact is rated 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. That covers most control-voltage rails in a panel.

Frequently asked questions

Where can I buy 3RT2016-1BB42-ZX95 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is the closest functional second-source for 3RT2016-1BB42-ZX95?

The closest peer in the same SIRIUS S00 family is 3RT2016-1AG62. Both are Size S00 power contactors with screw terminals and an auxiliary switch, but the coil voltage differs — 24 VDC on the -1BB42 versus 24 VAC on the -1AG62. The panel footprint and wire ranges are identical, so a swap requires changing the control voltage source, not rewiring the power circuit.

Will 3RT2016-1BB42-ZX95 drop into a panel specified around 3RT2016-1AG62 without rewiring?

Yes, the mechanical footprint is identical — same 45 mm width, 58 mm height, 73 mm depth, same DIN-rail clip, same screw-terminal layout. The only difference is the coil: 24 VDC on the -1BB42 versus 24 VAC on the -1AG62. If the panel already supplies 24 VDC, it drops in. If it supplies 24 VAC, you need a DC supply or a different coil variant.

MPN
3RT2016-1BB42-ZX95