Rated for DC-13 duty, it switches 10 A at 24 VDC, 2 A at 48 VDC, and 2 A at 60 VDC — the 48 V figure is the one that governs fit for a 48 VDC control circuit. At 400 VDC it handles 3 A. Mechanical life is typical 30 million operations; switching frequency tops out at 1000 cycles/hour in AC-1 duty and 750 cycles/hour in AC-3 or AC-3e duty, dropping to 250 cycles/hour in AC-4 for heavy jogging or plugging applications.
The 73 mm depth and 58 mm height fit within the Size S00 envelope, leaving room for auxiliary contact blocks on top.
Wiring and terminations
Main contact screw terminals accept solid or stranded wire from 0.5 to 4 mm², or two conductors per terminal: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². The coil terminals share the same wire range.