Skip to main content
Siemens 3RT2016-1BW42 — Contactors

Siemens 3RT2016-1BW42 SIRIUS Power Contactor, S00, 48 VDC Co

MPN3RT2016-1BW42
Active

Siemens SIRIUS 3RT2016-1BW42 power contactor, size S00, 48 VDC coil, screw-type terminals, 3-pole main contacts, integrated auxiliary switch, screw and snap-on 35 mm DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2016-1BW42 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1BW42 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1BW42 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-1BW42 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1BW42 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1BW42 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1BW42 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-1BW42 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1BW42 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm

Product details

Integrator's note: 3RT2016-1BW42

The Siemens SIRIUS 3RT2016-1BW42 is a size S00 power contactor — the smallest frame in the SIRIUS family, built for switching motor loads up to 3 kW at 400 V AC-3 duty. Coil is 48 VDC, screw-type terminals on both coil and main contacts. Integrated auxiliary switch (1 NO + 1 NC) is wired to the same terminal block, saving a separate aux block on the DIN rail.

Dimensions: 45 mm wide, 58 mm tall, 73 mm deep — fits standard S00 cutout in a 40 mm deep enclosure with clearance for wiring.

For doubled conductors: 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm². Strip length follows standard screw-terminal practice — no special tooling required. Main contacts are 3-pole (3 NO), rated for 20 A at 400 V AC-3e.

Rated for 1,000 operations per hour at AC-1 (resistive), 750 ops/h at AC-2 and AC-3 (motor), and 250 ops/h at AC-4 (plugging/inching). Switching times: DC coil pickup 7...13 ms, arcing time 10...15 ms.

Frequently asked questions

What is the closest functional alternative to 3RT2016-1BW42?

The 3RT2016-1BB41-ZW97 is a peer variant in the same S00 frame with the same main contact rating, but with a 24 VDC coil instead of 48 VDC. Panel fit and wiring are identical — swap the coil voltage and it drops in without rewiring the load side.

What are the key dimensions for panel layout?

Width 45 mm, height 58 mm, depth 73 mm. Requires 10 mm clearance above, below, and forward; 6 mm sideways. Mounts on 35 mm DIN rail per DIN EN 60715.

What wire sizes does this contactor accept?

Solid or stranded 0.5...4 mm² per screw terminal. For doubled conductors: 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm².

Can 3RT2016-1BW42 replace a 3RT2016-1BB41-ZW97 without rewiring?

Yes, physically and electrically — same S00 frame, same main contact configuration, same terminal layout. The only difference is coil voltage: 48 VDC vs 24 VDC. Verify your control voltage before swapping.

MPN
3RT2016-1BW42