It carries a 24 VDC coil with screw-type terminals, mounts on a 35 mm DIN rail per DIN EN 60715 via screw or snap-on, and occupies a 45 mm wide by 117 mm deep footprint. At 24 VDC the main contacts are rated for 6 A; derating applies at higher DC voltages — 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. These are the DC switching limits, not the AC motor ratings, and govern the part's use in DC load circuits. Switching frequency depends on duty: up to 1,000 cycles/hour in AC-1 (resistive), 750 cycles/hour in AC-2 and AC-3 (motor starting/running), and 250 cycles/hour in AC-4 (plugging/inching). The AC-3e rating also allows 750 cycles/hour.
Accepts solid or stranded wire: 0.5 to 4 mm² single, or 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and 2x 4 mm². The coil connection uses screw-type terminals.
The contactor's lifecycle stage is marked as current production. Mechanical endurance is typical 10,000,000 operations.