At 45 mm wide, it occupies a single modular slot in a DIN-rail panel layout, with 117 mm depth to account for wiring clearance and arc chamber volume.
Coil and switching characteristics
Maximum switching frequency varies by duty: 1,000 operations per hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor starting and running), and 250/h at AC-4 (plugging/reversing). The AC-3e rating also caps at 750/h.
Auxiliary contact ratings and operating conditions
This variant ships without an auxiliary switch block, but the main contact ratings at various DC voltages are specified: 6 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. These are the DC-13 (solenoid/electromagnetic load) ratings for the main contacts — useful when switching DC control loads directly.