The coil is 24 VDC with screw-type terminals, and the main contacts are rated for switching at several voltage levels: 6 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. At 230 V it carries a 1 hp motor load. These ratings define the actual load it can break — match your motor FLA against the appropriate voltage column. Mechanical switching frequency varies by duty: up to 1 000 cycles/hour at AC-1 (resistive), 750 cycles/hour at AC-2 and AC-3 (motor starting/running), and 250 cycles/hour at AC-4 (plugging/inching). For AC-3e the rate is also 750 cycles/hour. The arcing time is 10 to 15 ms at AC, and the contactor's typical mechanical life is 10 000 000 operations.
Dimensions are 45 mm wide, 58 mm high, and 117 mm deep — a standard S00 footprint that fits alongside other S00 contactors and overload relays on the same DIN rail. Wire terminations accept solid or stranded conductors from 0.5 to 4 mm², with dual-wire capability: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm².