Skip to main content
Siemens 3RT2016-1FB42-ZX95 — Contactors

Siemens 3RT2016-1FB42-ZX95 SIRIUS Power Contactor, Size S00,

MPN3RT2016-1FB42-ZX95

Siemens SIRIUS, Power contactor, 3RT2016-1FB42-ZX95, Size S00, 24 VDC coil, screw-type terminals, 45 mm width, 58 mm height, 73 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2016-1FB42-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1FB42-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1FB42-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-1FB42-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1FB42-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1FB42-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1FB42-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-1FB42-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1FB42-ZX95 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm

Product details

The coil is rated 24 VDC with a pickup threshold of 0.8 x rated value. Dropout timing on DC is 38 to 65 ms, and arcing time runs 10 to 15 ms.

The auxiliary switch is present, and the main contact wire range accepts solid 0.5 to 4 mm² and stranded 0.5 to 4 mm², with combinations up to 2x 4 mm² or 2x (0.5 to 1.5 mm²). Switching frequency limits depend on duty: AC-1 (resistive) allows up to 1,000 operations per hour; AC-3 (motor starting) and AC-3e both cap at 750 ops/h; AC-4 (plugging/inching) drops to 250 ops/h. These are the thermal limits of the contactor — exceeding them shortens life or causes welding. Rated operational current varies by voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. At 230 V the rating is 1 hp. These are the contact ratings for the auxiliary or main circuit depending on configuration. Mechanical life is typical 30 million operations. This affects how close you can pack adjacent devices on the DIN rail without derating.

Frequently asked questions

What is the closest functional second-source for 3RT2016-1FB42-ZX95?

The peer 3RT2016-1AK22 is a size S00 SIRIUS contactor with a similar footprint, but its coil is 24 VAC rather than 24 VDC. If your control voltage is DC, the 1FB42 is the correct variant; swapping to an AC coil without changing the supply will not hold in.

MPN
3RT2016-1FB42-ZX95