SIRIUS S00 coupling contactor for DC switching
The 3RT2016-1MB42-0KT0: The 24 VDC coil pulls in at 85 % of rated voltage (20.4 V) and drops out at 185 % (44.4 V), giving a wide operating band for control circuits with sag or transient overvoltage.
DC switching capacity and operating frequency
The arcing time for DC loads is 10–15 ms, and the minimum DC on-time is 5–20 ms — important for timing-sensitive circuits like brake coils or DC injection braking. The AC-3e rating matches the AC-3 figure at 750 cycles/hour.
No auxiliary switch is integrated — add a separate SIRIUS auxiliary contact block if feedback or status signaling is needed.