Skip to main content
Siemens 3RT2016-1QB41 — Contactors

Siemens 3RT2016-1QB41 SIRIUS Coupling Contactor, 24 V Coil,

MPN3RT2016-1QB41
Active

Siemens SIRIUS coupling contactor, size S00, 24 V DC coil, 10 A rated current, screw-type terminals, snap-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2016-1QB41 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1QB41 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1QB41 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-1QB41 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1QB41 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1QB41 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1QB41 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
3RT2016-1QB41 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1QB41 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth117 mm

Product details

Its 24 V DC coil pulls in at 0.7 of rated voltage and drops out cleanly — the 7 to 20 ms DC operate time and 10 to 15 ms arcing time are tight enough for sequenced starter groups without overlap. Rated at 10 A at 24 V DC for the main contacts, it handles 3 A at 400 V AC and 1 hp at 230 V AC — figures that cover small pumps, fans, and conveyor drives in a standard 400 V three-phase panel.

Frequently asked questions

Where can I buy 3RT2016-1QB41 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What is 3RT2016-1QB41's listed depth?

The depth is 117 mm, with a width of 45 mm and height of 58 mm.

What wire sizes does the 3RT2016-1QB41 accept?

The screw-type terminals accept solid or stranded wire from 0.5 to 4 mm², and up to 2x 4 mm² or 2x (0.5 to 1.5 mm²) with ferrules.

MPN
3RT2016-1QB41