SIRIUS coupling contactor, size S00, 24 VDC coil
The coil picks up at 0.85 of rated value and drops out at 1.85 of rated value. Screw-type terminals accept solid or stranded conductors from 0.5 to 4 mm², and the contactor mounts on 35 mm DIN rail per DIN EN 60715.
Switching capacity and duty cycle
Main contacts are rated for 20 A at 400 V AC (AC-1) and 12 A at 400 V AC (AC-3), so this contactor handles resistive loads up to 20 A and motor loads up to 12 A in the same voltage class. The DC switching capacity varies by voltage: 10 A at 24 V, 2 A at 48 V or 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. Maximum mechanical switching frequency is 1,000 cycles per hour at AC-1, 750 at AC-2 and AC-3, and 250 at AC-4 — the AC-4 figure governs frequent plugging or inching duty.
The contactor measures 45 mm wide, 58 mm high, and 73 mm deep — a compact S00 footprint that fits standard DIN-rail enclosures.