Skip to main content
Siemens 3RT2016-2AF01 — Contactors

Siemens SIRIUS 3RT2016-2AF01 Power Contactor, S00, 24 VDC co

MPN3RT2016-2AF01
Active

Siemens SIRIUS power contactor, size S00, 3RT2016-2AF01, 24 VDC coil, spring-type terminals, 45 mm wide.

$102.27Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2016-2AF01 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-2AF01 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-2AF01 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz110 V
3RT2016-2AF01 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-2AF01 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-2AF01 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-2AF01 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-2AF01 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-2AF01 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RT2016-2AF01 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

It switches motor loads in control panels and industrial machinery, with a 24 VDC rating of 10 A.

The 24 VDC coil pulls in reliably at 10 A, but the contactor also carries rated switching currents at higher voltages: 2 A at 48 VDC, 2 A at 60 VDC, 1 A at 110 VDC, 0.9 A at 125 VDC, 0.3 A at 220 VDC, 3 A at 400 VDC, and 0.2 A at 440 VDC. At 230 VAC it is rated for 1 hp motor load. These numbers define the DC load curve — the contactor can handle moderate DC switching, but the current drops sharply as voltage rises, typical for a contactor sized for AC motor duty. Spring-type terminals accept solid or stranded wire from 0.5 to 4 mm², and can take two conductors of the same range (2x 0.5...4 mm²). That is a clean, tool-less termination — no screwdriver needed for the power circuit, which speeds up panel wiring.

The contactor measures 45 mm wide, 70 mm tall, and 73 mm deep.

Frequently asked questions

What wire sizes does the spring terminal accept?

Solid or stranded wire from 0.5 to 4 mm², and can take two conductors of the same range (2x 0.5...4 mm²).

What are the mounting dimensions and clearance requirements?

The contactor is 45 mm wide, 70 mm tall, and 73 mm deep. It mounts on a 35 mm DIN rail. Required clearances: 10 mm upwards, 10 mm downwards, 10 mm forwards, 6 mm at the side.

MPN