The 24 VDC coil with spring-type terminals means no screwdriver needed for the coil wiring — strip, push, done. Dimensions are 45 mm wide, 70 mm tall, 73 mm deep — fits the standard S00 footprint on 35 mm DIN rail per DIN EN 60715.
That 6 mm side gap is tight — if you're packing multiple contactors side-by-side, keep that minimum for heat dissipation and arc clearance.
Switching capacity and operating rates
Main contacts rated for AC-1 resistive loads up to 1,000 operations per hour, AC-3 motor switching at 750 ops/h, and AC-4 (plugging/inching) at 250 ops/h. Mechanical life is listed at 30 million operations typical. Arcing time runs 10 to 15 ms.
Environmental range
The storage limit is what governs handling and shipping, not running. If your panel sees ambient above 60 °C, you'll need to derate or move to a larger frame.