3RT2016-2AK62-ZX95 - Siemens
CONTACTOR, AC-3, 4KW/400V, 1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S00 SPRING-LOADED TERMINAL REUSABLE PACKAGING 120 PIECES
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S00 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 8.5 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 1 hp |
| Rated value @ 24 V | 10 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | AC |
| Rated value @ 50 Hz | 0.24 |
| Rated value @ 50 Hz | 110 V |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA) |
| Short-circuit coordination type 2, fuse | gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | spring-loaded terminals |
| Aux. / control circuit connection | spring-loaded terminals |
| Conductor cross-section, solid | 0.5 ... 4 mm² |
| Conductor cross-section, solid or stranded | 2x (0,5 ... 4 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 2.5 mm²) |
| Mounting method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 30 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 70 mm |
| Depth | 73 mm |
| Parameter | Value |
|---|---|
| At AC | 7 ... 13 ms |
Frequently asked questions
What is the coil voltage of the Siemens 3RT2016-2AK62-ZX95 contactor?
Buyers must confirm AC110V 50Hz / 120V 60Hz coil matches their control circuit before ordering.
What does the -ZX95 suffix mean on a Siemens 3RT2016 contactor?
The suffix denotes the reusable 120-piece bulk packaging option, affecting MOQ and unit cost.
What is the difference between 3RT2016-1AK61 and 3RT2016-2AK62-ZX95?
Distinguishes connection type (screw vs spring) and packaging, key for retrofit and stocking decisions.
How many contactors are included in the 3RT2016-2AK62-ZX95 reusable packaging?
Confirms 120-piece pack quantity so buyers can plan inventory and per-unit economics.
What is the equivalent Siemens Sirius contactor for 3RT2016-2AK62-ZX95 with screw terminals?
Engineers needing screw-terminal equivalents must cross-reference MPNs to avoid redesign.
Where can I buy 3RT2016-2AK62-ZX95 in stock with authorized traceability?
Ensures genuine Siemens stock with documentation, critical for industrial warranty compliance.