Skip to main content
Siemens 3RT2016-2AP01 — Contactors

Siemens 3RT2016-2AP01 SIRIUS Contactor, Size S00, 45 mm Wide

MPN3RT2016-2AP01
Active

Siemens SIRIUS 3RT2016-2AP01 power contactor, Size S00, 45 mm width, 73 mm depth, spring-type coil terminals, screw and snap-on 35 mm DIN rail mounting.

$112.73Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2016-2AP01 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-2AP01 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-2AP01 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz230 V
3RT2016-2AP01 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-2AP01 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-2AP01 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-2AP01 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-2AP01 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-2AP01 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RT2016-2AP01 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

The 3RT2016-2AP01 is a Size S00 SIRIUS power contactor — the smallest frame in the family, at 45 mm wide, 70 mm tall, and 73 mm deep. That footprint fits standard 45 mm-wide DIN-rail slots; you can pack multiple units side by side without oversizing the enclosure. These are the air-gap and creepage distances for the rated voltage — respect them to avoid flashover between adjacent devices.

Wire termination and coil connection

The coil connection uses spring-type terminals — push-in for solid or ferruled stranded, no screw tightening needed.

Switching duty and mechanical life

Maximum switching rates: 1,000 operations per hour in AC-1 (resistive), 750 ops/h in AC-3 and AC-3e (motor starting), and 250 ops/h in AC-4 (plugging/inching). These are the thermal limits of the contactor — exceeding them shortens contact life or causes welding. An auxiliary switch is built in, with main contact configuration options between 20 and 12 (likely NO/NC combinations). Confirm the exact auxiliary contact arrangement from the full datasheet before wiring.

Environmental limits and lifecycle

The contactor is rated for indoor use in a typical control panel environment.

Frequently asked questions

How do I get current pricing and availability for 3RT2016-2AP01?

Submit an RFQ with your target quantity. We source this active part through authorized distribution and confirm current pricing and lead time at quote. No stock-holding claim; quoted per order.

What compliance documentation does Siemens provide for 3RT2016-2AP01?

The evidence does not list specific compliance marks (UL, CSA, CE, RoHS, REACH) for this exact order code. Standard Siemens SIRIUS contactors typically carry CE and UL/CSA certifications; request the manufacturer's declaration of conformity with your RFQ for project documentation.

MPN
3RT2016-2AP01