Skip to main content
Siemens 3RT2016-2JB42 — Contactors

Siemens 3RT2016-2JB42 SIRIUS Coupling Contactor, 24 VDC, S00

MPN3RT2016-2JB42
Active

Siemens SIRIUS, coupling contactor, size S00, 24 VDC coil, spring-type terminals, 45 mm width, 73 mm depth, 70 mm height, rated 10 A at 24 V.

$22.86Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2016-2JB42 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-2JB42 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-2JB42 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2016-2JB42 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-2JB42 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-2JB42 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-2JB42 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
3RT2016-2JB42 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-2JB42 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm

Product details

Integrator note — SIRIUS 3RT2016-2JB42 coupling contactor

The Siemens 3RT2016-2JB42 is a SIRIUS coupling contactor in the S00 frame — purpose-built for switching auxiliary or signal circuits where galvanic isolation between control and load is needed, not for heavy motor starting. The 24 VDC coil pulls in at 0.7 × rated and drops out reliably; spring-type terminals on both coil and main contacts accept 0.5–4 mm² solid or stranded, which is the typical range for control wiring up to 4 mm². The S00 footprint — 45 mm wide, 73 mm deep, 70 mm high — fits standard 35 mm DIN rail (DIN EN 60715) with screw or snap-on fastening. Clearances: 10 mm upward/downward/forward, 6 mm at the sides.

The headline switching capacity is 10 A at 24 V — that's the resistive load rating at the coil voltage. For DC loads at higher voltages, the curve drops: 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. There's also a 1 hp rating at 230 V, likely for single-phase motor loads. Operating frequency varies by duty: up to 1,000 cycles/hour at AC-1 (resistive), 750 at AC-2 and AC-3 (motor starting), and 250 at AC-4 (plugging/inching) (–,). The auxiliary switch is not fitted — this is a bare contactor, so add a separate auxiliary block if you need feedback.

DIN-rail integration

The S00 width of 45 mm is the narrowest in the SIRIUS contactor family.

Frequently asked questions

What is 3RT2016-2JB42's depth?

The depth is 73 mm. The overall dimensions are 45 mm width × 73 mm depth × 70 mm height, fitting the S00 frame.

What wire sizes does the 3RT2016-2JB42 accept?

Spring-type terminals accept 0.5–4 mm² solid or stranded, and dual-wire entry allows 2× (0.5–4 mm²). No ferrule requirement is stated, but stranded wire with ferrules is standard practice.

MPN
3RT2016-2JB42