SIRIUS Size S00 Power Contactor
Mounting is via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, with clearances: 10 mm upward, 10 mm forward, 10 mm downward, and 6 mm at the side. The standing mounting position on a horizontal surface is specified.
Switching frequency varies by duty: AC-1 (resistive) at 1 000 operations/hour maximum, AC-2 and AC-3 (motor starting/running) at 750 ops/hour, and AC-4 (plugging/inching) at 250 ops/hour. Auxiliary contact ratings are specified at multiple voltages: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. The 230 V rating is given as 2 hp.